DC UPS Battery sizing calculations

DC UPS Battery Sizing

The battery ampereshour capacity shall be computed by the following formula:

                                                                      𝑨𝑯(𝑼𝑷𝑺)=𝑳×𝑩𝑻×𝑻𝑪×𝑨𝑭×𝑫𝑭

AH(UPS) – Battery Capacity

L – Load Current

BT – Battery Backup Time (Hrs)

TC – Temperature Compensation Factor

AF – Battery Aging Factor

DF- Design Factor

DC UPS Battery Capacity:

𝐴𝐻(𝑈𝑃𝑆)=𝐿×𝐵𝑇×𝑇𝐶×𝐴𝐹×𝐷𝐹

Example:

L= 45.45A, BT= 4.00 Hrs, TC = 1, AF = 1.25, DF= 1.10

𝐴𝐻(𝑈𝑃𝑆)=45.45×4×1×1.25×1.10

𝑨𝑯(𝑼𝑷𝑺)=𝟐𝟒𝟗.𝟗𝟕 𝑨𝒎𝒑𝒆𝒓𝒆−𝒉𝒐𝒖𝒓

(For Four Hours Battery Back-up)

DC UPS Battery Charging Sizing

The current rating of UPS battery charge sizing shall be calculated by the following formula

                                                                        𝐴𝐻(𝑏𝑐)=(𝑆𝐹×𝐿)+((𝐵𝐼𝐹)×(𝐴𝐹/𝑅𝑇))

 Where,

A(bc) – Ampers rating of charger

SF – Service Factor

AH – Battery Capacity

RT – Recharge Time

L – Load Current

BIF – Battery in efficiency factor

Example

SF- 1.10, AH – 270.00, RT- 8.00 hrs, L – 45.45A, BIF – 1.15

𝐴𝐻(𝑏𝑐)=(1.10×45.45)+((1.15)×(27/08))

𝐴𝐻(𝑏𝑐)=88.80 𝐴𝑚𝑝𝑒𝑟𝑒𝑠