Table of Contents
ToggleCircuit wiring practice
The entire wiring of circuitry for indications, alarms, metering and protection should be permanent wiring.
There is no place for temporary wiring or adhocism in Relay circuitry.
The leads should be identified by ferrules near terminals.
Every lead should end at a terminal point and no junctions by twisting is allowed. If two wires are to be terminated at same terminal they may be connected at two different terminals and a loop provided.
The wiring should be by copper leads for C.T secondaries for all cores (i.e.) metering as well as protection.
The wiring should be by copper leads for PT secondaries also wherever they are intended for protection.
The copper lead for above should be stranded but not single lead type.
Aluminum leads can be used for indication, alarms and PT secondaries for metering but stranded wires only are to be used. However where PTs are employed for commercial metering, stranded copper wires are to be used.
The terminations should be lugged by ring shape ‘O’ lugs. ‘U’ shape lugs should be avoided.
For CT Secondary terminations, two nuts with one spring washer and two flat washers to be compulsorily used.
The terminal strips should be stud type with nuts and not screw-in-type.
Wherever two batteries are available, the primary protection and back-up protection should be from different batteries.
Where there is only one battery at a Power Substation, the primary and back-up protections should be given D.C supply through two individual circuits with independent fuses run from D.C bus. 1.13A When CBs have two trip coils, both main protection and backup protection will energise both the trip coils.
D.C and A.C supplies should not be taken through different cores of the same cable.
Independent D.C cables should be run to every equipment in the yard and looping of D.C supply either in the yard or in the control room from one equipment to the other is not permitted.
The D.C yard lighting for emergency lighting should be through independent cables and not mixed up with protection and other circuitry.
For indications, alarms, annunciations, controls (closing coil, trip coil, etc. negative (-ve) is always given direct and positive (+ve) is supplied only ‘on commands’ like close, trip, relay trip, etc.
Where D.C protection supply is at 24 volts or 32 volts, the battery units should be very near the equipment and not in the control rooms.
In cases of 1.18 above, each tripping units (24 volts or 32 volts battery with charger) should not be used for more than two circuit breakers or equipment.
Standard colour codes for leads in control cable of different sizes should be as denoted on the cover page.
The lead numbers are also standardised as follows so that any MRT Engineer can easily identify the purpose for which the lead is connected by noting the lead number.
J Series | D.C Incoming . | J1, J2, etc. |
K Series | Control - Closing, Tripping, etc. | K1, K2, K3 etc. |
L Series | Alarms, indications and annunciations | L1, L2, L3, etc. |
E Series | Potential transformer secondaries | E1, E2, E3, etc. |
H Series | LT A.C Supply | H1, H2, H3, etc. |
A Series | C.T secondary for special protection | A1, A2, A3, etc. |
B Series | Bus bar protection | B1, B2, B3, etc. |
C Series | Protection Circuits | C1, C2, C3, etc. |
D Series | Metering Circuits | D1, D2, D3, etc. |
CTs with 1 amp secondary rating should be used compulsorily where meters, protective devices etc. are remotely situated with reference to equipment.
The CT ratios available and adopted with number of cores shall be displayed on each panel as follows: (with underlined position as adopted). 1200 – 600 – 300-150 / 1-1-1-1.
Wherever CT cores are not used “SHORTING LOOPS” should be provided near CT secondary terminals and not in marshaling boxes or at panels.
The Cable entries near equipment, marshaling boxes and panels should be by use of appropriate size glands.
The Wiring inside the panels should be clear and neatly fastened avoiding loose wires. 1.27 All wires not in use should not only be disconnected but removed from panels.
PT secondaries should have group MOCBs with D.C alarm. Fuses at different panels should not be used.
Few cells from a battery of cells should not be used for separate low voltage D.C circuits. D.C – D.C converters only should be employed utilising full D.C voltage of the entire battery as input.
Standard Protection lead Number
Certain lead numbers are standardised as follows and should be compulsorily adopted with ferrules at terminations of leads. J1 – DC Positive J2 – DC Negative
Controls & Alarms Remote
Close : K15R Remote Trip : K5R Local Close : K15L Local Trip : K5L
Types of Control Panels and Junction Box
Control Panels, Relay Panels, Control & Relay Panels, Synchronising Panel or Trolley, Communication Panels, Annunciation Panels, A.C & D.C. Distribution Board, Charger Panels, Relay Galleries, Auxiliary Control Panels, Marshalling Boxes, AMG Panels, Machine Panels, Duplex(HV,LV) Panels, Bus Zone Protection Panels, RTCC Panels (OLTC), RTI Panels (temp), Indoor Panels, Outdoor Panels, Panels with drawn up mimics & isolator cum breaker status indication (Semaphores) etc. PMU Panel, RTU Panel, Under/Over Frequency Panel, NIFPS box, CT Junction Box.
Device Number and their nomenclature
2 | Time delay relay |
3 | Checking or Interlocking relay |
21 | Distance relay |
25 | Check synchronizing relay |
27 | Undervoltage relay |
30 | Annunciator relay |
32 | Directional power (Reverse power) relay |
37 | Low forward power relay |
40 | Field failure (loss of excitation) relay |
46 | Negative phase sequence relay |
49 | Machine or Transformer Thermal relay |
50 | Instantaneous Overcurrent relay |
51 | A.C IDMT Overcurrent relay |
52 | Circuit breaker |
52a | Circuit breaker Auxiliary switch “Normally open” (‘a’ contact) |
52b | Circuit breaker Auxiliary switch “Normally closed” (‘b’ contact) |
55 | Power Factor relay |
56 | Field Application relay |
59 | Overvoltage relay |
60 | Voltage or current balance relay |
64 | Earth fault relay |
67 | Directional relay |
68 | Locking relay |
74 | Alarm relay |
76 | D.C Overcurrent relay |
78 | Phase angle measuring or out of step relay |
79 | AC Auto reclose relay |
80 | Monitoring loss of DC supply |
81 | Frequency relay |
81U | Under frequency relay |
81O | Over frequency relay |
83 | Automatic selective control or transfer relay |
85 | Carrier or pilot wire receive relay |
86 | Tripping Relay |
87 | Differential relay |
87G | Generator differential relay |
87GT | Overall differential relay |
87U | UAT differential relay |
87NT | Restricted earth fault relay |
95 | Trip circuit supervision relay |
99 | Overflux relay |
186A | Auto reclose lockout relay |
186B | Auto reclose lockout relay |
