Welcome to Electrical World

Trouble Shooting chart of D.C. Machines

Trouble Shooting chart of D.C. Machines

Symptom

Possible Cause of
Trouble

Solution

Failure to build up of
voltage (dc generator)

>Faulty Voltmeter, check output voltage with separate voltmeter. Open field
resistor.
>Open field circuit. Check coils for open circuit or loose connections.
>Absence of residual magnetism in self excited generator.
>Dirty commutator, high mica, brushes not having good contact with commutator.
>New brushes seated but not contacting sufficient area. Armature shorted internally
to ground.

>Replace voltmeter. Replace
or repair resistor Replace defective coils, tighten or solder loose connections.
>Flash the field. Connect battery to field with correct polarity Allow current momentarily and cut off.
Field will resume residual magnetism.
>Under cut mica, clean or dress commutator.
>Replace or reseat brushes, free if binding in holders.
>Brush bedding and reseat brushes. Remove, test and repair or replace.

Output voltage too low
(dc generator)

>Grounded or shorted field coil.Shorted filtering capacitor; open filter choke, open ammeter shunt, broken brush shunts.
>Prime mover speed low(check speed)
>Brushes not seated properly.Commutator dirty, or film too heavy

>Test, repair or replace.
>Adjust governor on prime mover. Reseat brushes.
>Clean commutator with fine
sand paper. Replace brushes with proper grade set or Use complete new set of brushes
>Adjust properly. Connect properly

Output voltage too
high (dc generator)

>Field resistor not properly
adjusted
>Reversed field coil or armature coil connections Prime mover speed too high.
>Faulty voltage regulator
Overloaded.

>Adjust governing device.
>Adjust or replace faulty voltage regulator.
>Check speed.

Armature too hot

>Check meter readings against name plate rating.
>Excessive brush pressure.
>Belt too tight, or coupling not
aligned.
>End plate out of position.
Bent shaft.
>Armature coil shorted Armature striking poles. Check bearing for play and air gap for proper spacing, shaft for bent condition.
Poor ventilation.Clogged air passages.
>Repeated changes in load in bulk. Observe meter readings.

Reduce load.
>Adjust pressure or replace tension springs.
>Adjust belt. Align units properly.
>Assemble correctly.
>Straighten on lathe or replace.
>Repair or replace armature. Replace bearings. Straighten shaft or replace armature.
>Clean clogged air passages. Provide clearance. For circulation of air around equipment. Clean equipment.
>Faulty design. Generator should be used in steady load application.

Field coils hot

>Shorted or grounded coils. Poor ventilation.
>Overload (compound generator) check meter readings against name plate data.

>Replace shorted coils; grounded coils may be repaired.
>Clean clogged air passages.
>Provide clearance for air circulation around equipment.
>Reduce load.

Sparking at brushes

>Brushes off neutral plane. Brushes not seated properly. Dirty brushes and commutator High mica, Rough or eccentric commutator. Open in armature
>Grounded, open or shorted field winding
>Lack of brush pressure; brushes sticking in holder
>Selective commutation caused by unequal brush tension
>Open circuit in field Rheostat

>Set rigging so that brushes are in proper plane.
>Reset.
>Clean.
>Under cut; Resurface commutator, Repair/ replace armature.
>Repair or replace defective coil/coils.
>Replace tension springs, clean holders.
>Adjust spring tension, Replace brushes or shunts.
>Replace or repair Rheostat.

Common defects in commutators

A good commutator will have a smooth polished surface dark chocolate brown in colour.

Commutator surface pitted and rough : This is mostly the result of excessive sparking, The surface may be smoothened with fine sand paper on a curved block and polished with crocus cloth. Never use emery paper or cloth, as the fine emery particles may get to the commutator.

Ridge formation on commutator : Ridges are formed if the brush holders on different rocker arms are not properly staggered. Another possible cause in the case of large armatures is, if the armature does not oscillate to the extent of about 1/8 in. axially on either side of the core centre. The ridges may be filed off by a smooth file, or by means of specially shaped commutator grinding stones, whose curvature corresponds to that of the commutator.

If it is a generator, remove all carbon brushes and run it up, If it is a motor, run up to full speed, switch off the supply and quickly apply the grinding stone to the surface of the commutator, while the armature is slowing down. Quite a lot of metal can be removed this way if the work is properly done by a trained hand. After grinding is over, finish off with smooth sand paper and crocus cloth.

If the commutator surface is very bad, then the armature should be put on a lathe and skimmed, after checking the trueness of the shaft by a dial indicator. The cuts should be the lightest possible. The final cut should preferably be by a diamond tipped tool with fine cuts of the order of .0005 to .001 in. with a feed of 500 threads per in. Finally, mica should be undercut as usual.

Commutator is eccentric or having high bars and low bars : Excessive blackening or burning of a few commutator bars only shows presence of high or low bars, mostly caused by the bolts holding the commutator V-ring becoming slack. The bolts should be tightened up fully, after the commutator has run in for some time and is fully warm. After this is done, the commutator should be skimmed on a lathe. If only a portion of the commutator surface shows signs of severe sparking, it is a clear sign of the commutator being eccentric. No commutator should show a variation of more than 0.0254mm (.001 in.) when checked by a dial indicator, when mounted on its bearings on the motor.

Protecting mica between bars : All commutators should have the mica between the bars undercut to a depth of 0.8mm (1/32 in.) approximately. After grinding or turning of the commutator, undercutting should invariably be done either manually or by a machine. It is essential to round off the sharp edges of the bars, and remove all bars, as also to thoroughly clean the mica slots and blow off all dust. Undercutting should also be done periodically.

Flashover of commutator: Flashover across commutator is frequently caused by heavy accumulation of dust over the commutator surface or due to low-resistance leakage path either in the commutator risers, or between the bars or at the sides of the commutator. Such a flashover constitutes a dead short across the mains and before the fault is isolated by the circuit-breaker, the heat generated may be so much as to cause appreciable damage to the commutator surface and the surrounding area. The dust and dirt should be cleaned by washing and brushing with petrol; all carbonized matter, foreign particles and deposits should be scraped off. The inter-segment gaps should be kept clean; otherwise they may get filled up with dirt or carbon causing sparking and further carbonization.

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top