Welcome to Electrical World

Types of Circuit Breaker testing and SF6 breaker testing

Circuit Breaker Insulation Resistance Test

Use Megger to measure insulation resistance.

Insulation Resistance Tests to be done:

Pole – Pole ( CB in open position )

Phase-Earth (CB in Closed Condition)

Phase to Phase(CB in closed condition)

The IR value should be > 500 MΩ

Circuit Breaker Timing Test

Circuit Breaker Timing Test

Closing time: The time interval between energizing the coils of the breaker (when CB contacts are in open position) and the instant when the contacts touch each other.

Opening time: It is opposite to that of closing time. It is the time interval between energizing the trip coil (CB contacts are in open position) and the instant when contacts separate from each other.

Procedure

De- energize, discharge the equipment which is to be tested as a safety precaution.

Check whether Timer leads and associated clips that are to be connected to the breaker poles are good & tight.

Make the test connections on the lines of circuit diagram

Switch on the power supply to the timer and issue Close command from the timer. Note down the close timing displayed on the timer

After recommended time interval (3 seconds), issue Open command from the timer. Note down the open timing displayed on the timer.

Now issue Close-Open (CO) command from the timer. Note down the CO timing displayed on the timer.

Circuit Breaker contact resistance test

Circuit Breaker contact resistance test

Due to the making and breaking of contacts at high speed and pressure, the contacts can be damaged.

Due operation of breaker, sparking occurs which can depreciate the contacts.

Sparking results in carbon formation which accumulates on the surface of contact and can increase in its resistance.

Due to increase in resistance of contacts, the I2R losses increase. Rise in contact resistance illustrates some abnormality in contacts of breaker therefore contact resistance test is performed.

Operating principle of this test depends upon balancing bridge (like Wheatstone bridge) and Ohms law. High current is injected and small voltage is applied to measure contact resistance.

Testing procedure

De-energize and discharge equipment which is to be tested as a safety precaution.

In case of the breaker make sure that Breaker/ isolated is isolated and kept in closed condition.

Make all the contact clean & connect current / voltage lead as shown below

Check the Firmness of the connections as loose connections may give erroneous results.

Switch on the power supply to the CRM and wait for the displayed values to become steady.

Repeat the test 2-3 times to get the steady value.

Repeat the same procedure for another phase in case of breaker.

 It is a DC current injection measurement method where 100 A dc is injected to measure DC resistance of the breaker / Isolator contact.

Standard values of the contact resistance are in the range of 25-60 micro-ohms

Circuit Breaker Dynamic contact resistance test

DCRM is a signature of an individual contact.Circuit breaker will have six signatures. DCRM signature is  initially recorded at the time of commissioning of the circuit breaker and repeated two yearly.The signatures are compared and abnormalities if any has to be observed.

The dynamic contact resistance measurement also involves travel measurement. With this travel velocity of the contacts while opening and closing can be obtained.contact resistance variation is plotted during the c-o operation of the circuit breaker.The variation in the resistance at the time of making of contacts and breaking of contacts can be observed.The variation in the resistance at the time of making of contacts and breaking of contacts can be observed.

Dynamic-contact resistance measurement method that has been validated by field tests which were performed on SF6 gas circuit breakers. The new method is based on the breaker contact resistance measurement during an opening operation and closing operation.

The measurement is performed by injecting DC current through the breaker and simultaneously monitoring the voltage drop as well as current flow during the operation of the breaker. From these two parameters a resistance value can be calculated.

Dynamic Contact resistance Signature is a non –invasive diagnosis measurement which indicates the erosion of arcing and main contacts looseness, damage, misalignment and helps to measure length of arcing tip. DCRM signature with travel curve gives fairly good idea about healthiness of main and arcing contacts.

The abnormal wear and tear or excessive pitting of arcing contact is indicated in the signature. Certain mechanical weaknesses, undetected by travel measurement are reflected in DCRM signature. It also gives prior indication of deterioration of operating mechanism linkages. Comparison with old signature makes condition monitoring and corrective measure possible.

Circuit Breaker Dew Point Testing

Dew point of arc quenching medium either sf6 or air has to be monitored at regular intervals.Dew point indicates the quality of the sf6 gas /air.dew point indicates the quality of the sf6 gas /air.Insulating properties remains unaltered if the ingress moisture is limited.Hence the dew point of the sf6 gas has to be monitored.

Requirement other Check point in Circuit Breaker

coil resistance measurement.

Leakage check of sf6 gas

Ir value of control circuit

CB operation counter healthiness

Oil/air pressure drop test

Oil/air pressure leakage in 24 hrs

Spring charging time 

Blocking/ deblocking setting of oil/air pressure switches has to be check for Tripping circuit I&II, closing circuit, auto reclose circuit, Low pressure alarm, compressor ON/OFF.

Blocking and deblocking of sf6 pressure /density monitor for low pressure alarm and CB lockout circuit.

Check healthiness of tripping circuit and annunciator and indication circuit.

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top